CJan Fluid Technology Co., Ltd.

BLOG

How to Select Liquid Cooling Hose Size: Flow Rate, Pressure Drop and Rack Cooling Requirements

2026/08/19Clicks:14

How to Select Liquid Cooling Hose Size: Flow Rate, Pressure Drop and Rack Cooling Requirements

Introduction

When engineers select a liquid cooling hose for an AI server rack, the first question is often:

What hose diameter should I use?

It sounds simple. In practice, hose diameter is determined by several variables:

  • Rack heat load
  • Required coolant flow
  • Coolant properties
  • Temperature difference
  • Hose length
  • Internal diameter
  • Fittings
  • Quick disconnects
  • Allowable pressure drop

A hose that physically fits a connector may still be the wrong hydraulic size. For AI data center cooling, the better approach is to start with the cooling requirement and work backward toward the hose specification.


1. Start With Rack Heat Load

The cooling system exists to remove heat. Therefore, hose sizing should ultimately relate to the heat generated by the equipment.

A simplified relationship is:

Heat removal ≈ coolant flow × coolant specific heat × temperature rise

In practical engineering terms:

Rack Heat Load

Required Heat Removal

Coolant Flow Rate

Hose Internal Diameter

Pressure Drop

CDU Pump Requirement

This sequence is much more useful than starting with the hose connection.

2. Why AI Rack Power Matters

Traditional data center racks may have relatively moderate thermal loads. AI racks are different. High-performance GPU systems can create substantially higher heat density, making liquid cooling attractive because coolant can transport heat much more effectively near the heat source.

As rack power increases, the cooling system may require:

  • Higher coolant flow
  • Larger flow passages
  • Lower hydraulic resistance
  • More efficient cold plates
  • Higher-capacity CDUs

The hose is only one part of this hydraulic network, but its internal diameter directly affects flow resistance.

3. Internal Diameter Matters More Than Nominal Connection Size

This is one of the most important points in hose selection. A connector may be described as:

  • 3/4 inch
  • 1 inch
  • 1-1/4 inch

But that does not necessarily tell you the actual flow capacity of the complete hose assembly. The engineer should check:

Actual hose ID + fitting ID + QD flow passage

For example:

CDU

│ 1" connection

Fitting


Hose ID


QD internal passage


Manifold

If one component has a substantially smaller internal passage, it can become a hydraulic restriction.

Show how changing hose internal diameter affects coolant velocity and pressure drop.

4. Coolant Flow Rate Is a Primary Sizing Parameter

The required flow rate depends on:

  • Heat load
  • Coolant type
  • Supply temperature
  • Return temperature
  • Desired temperature rise

For a simplified water‑based cooling calculation:

Q ≈ P / (Cp × ΔT)

Where:
Q = coolant mass flow rate
P = heat load
Cp = specific heat capacity
ΔT = allowable coolant temperature rise

The exact calculation should use the actual coolant properties and engineering units specified by the system designer.

5. A Simple Example

Suppose an AI cooling loop must remove 100 kW of heat and the design allows a coolant temperature rise of 10°C. For water‑based cooling, the required flow is roughly on the order of:

2.4 L/s, or approximately 144 L/min.
Note: This is only an illustrative engineering calculation. Actual systems must account for coolant composition, actual specific heat, density, operating temperature, CDU efficiency, cold plate performance, and total system pressure drop.

The example demonstrates an important principle: High rack heat load can require substantial coolant flow, which directly influences hose diameter.

6. Hose Diameter and Pressure Drop

Increasing hose diameter generally reduces flow resistance. Reducing diameter generally increases flow velocity and pressure loss.

A simplified relationship is:

Smaller ID

Higher Flow Velocity

Higher Pressure Loss

while:

Larger ID

Lower Flow Velocity

Lower Pressure Loss

However, simply choosing the largest available hose is not necessarily the best solution. Larger hoses can introduce:

  • Higher material cost
  • Larger fittings
  • Greater bending requirements
  • More installation space
  • Increased coolant volume

The objective is appropriate sizing, not maximum sizing.

7. Hose Length Also Affects Pressure Drop

Two hoses with the same internal diameter can have different hydraulic performance if their lengths differ.

1 m hose → Lower friction loss
5 m hose → Higher friction loss

This becomes important when a CDU is positioned far from the rack. Long routing may increase:

  • Pressure loss
  • Coolant volume
  • Installation complexity

Therefore, hose length should be included in the hydraulic calculation.

8. Don't Forget the Fittings

The hose is not the only source of pressure loss. A complete cooling assembly may contain:

  • Hose
  • Elbows
  • Adapters
  • Quick disconnects
  • Valves
  • Manifolds

The system pressure loss can therefore be considered conceptually as:

ΔP total = ΔP hose + ΔP fittings + ΔP QD + ΔP valves + ΔP manifold + ΔP cold plate

This is particularly important in high‑flow AI cooling systems.

9. Quick Disconnects Can Become a Restriction

Quick disconnect couplings are extremely useful for rack maintenance. However, engineers should not assume that all QDs have the same hydraulic performance.

Two couplings with the same nominal connection size may have different:

  • Internal flow passages
  • Pressure drop
  • Valve structures
  • Flow coefficients

Therefore, when specifying a liquid cooling assembly, request the QD's hydraulic performance data where available.
Show that pressure drop comes from the entire cooling loop rather than the hose alone.

10. Hose Diameter Selection Should Follow the Cooling Architecture

A typical AI cooling system might look like:

The required hose size may therefore differ at different points.

Location Typical Design Consideration
CDU → Rack Higher flow, longer routing
Rack → Manifold Flow distribution
Manifold → Cold Plate Branch flow
Cold Plate → Manifold Return flow
Manifold → CDU Combined return flow

There is no reason to assume that every hose in the system must have the same diameter.

11. Supply and Return Hoses

Supply and return hoses normally carry similar total system flow at the corresponding point in the loop. However, their operating conditions may differ slightly depending on architecture.

Engineers should consider:

  • Supply temperature
  • Return temperature
  • Pressure
  • Flow
  • Hose routing

Both should be specified as part of the complete cooling loop.

12. Avoid Selecting Hose Size From Existing Hardware Alone

A common situation is:

“The CDU has a 1‑inch port, so we need a 1‑inch hose.”

That can be a reasonable starting point—but it is not a complete engineering specification. The actual requirement may be influenced by:

  • Port geometry
  • Fitting internal diameter
  • QD passage
  • Hose ID
  • Required flow
  • Pressure drop

The correct question is:

Can the complete connection deliver the required flow within the allowable pressure drop?

13. Consider the Hose Bend Radius

Hydraulic sizing is not the only concern. A hose may have the correct ID but still be unsuitable if it cannot be routed properly.

A tight bend can:

  • Restrict flow
  • Increase mechanical stress
  • Reduce hose service life
  • Place stress on fittings

Therefore:

Hydraulic sizing + mechanical routing must be evaluated together.

14. Flexible Hoses Need Installation Space

AI racks are becoming increasingly dense. Space is occupied by:

  • Power distribution
  • Network cables
  • Cooling manifolds
  • Server hardware
  • Monitoring equipment

The selected hose diameter should therefore balance hydraulic requirements against installation space. This is one area where highly flexible hose constructions can provide a practical advantage.

Note: CJAN currently positions its LCH‑SDS product as an ultra‑flexible fire‑resistant EPDM hose for data center liquid cooling, specifically addressing applications where routing flexibility is important.

15. How to Select a Hose Size: Practical Workflow

For an AI liquid cooling project, the following workflow is useful.

Step Action
1 Determine heat load – Example: Rack = 100 kW
2 Determine coolant – Example: Water‑based coolant
3 Determine allowable ΔT – Example: 10°C
4 Calculate required flow – Use actual coolant properties
5 Establish allowable pressure drop – Based on CDU/pump capability
6 Evaluate hose ID – Compare candidate diameters
7 Add fittings and QDs – Calculate complete assembly pressure loss
8 Check mechanical installation – Verify bend radius, length, routing, connection orientation
9 Confirm safety margin – Check pressure rating, temperature rating, material compatibility, assembly performance

Create a visual decision process from rack heat load to final hose selection.

16. Example Hose Selection Matrix

The following is a design framework rather than a universal sizing table.

Cooling Requirement Initial Design Direction
Low rack heat load Smaller flexible hose may be sufficient
Medium rack heat load Medium ID with controlled pressure drop
High rack heat load Larger ID / low‑resistance assembly
Long CDU‑to‑rack route Pay particular attention to pressure loss
Compact rack Prioritize flexibility and bend radius
High flow Evaluate hose + QD + fitting as a system
High‑purity coolant Evaluate fluoropolymer options
Fire‑resistance requirement Consider dedicated fire‑resistant hose constructions

17. Material and Size Must Be Selected Together

Hose size cannot be separated completely from hose construction.

Material Considerations
EPDM Often attractive for water‑based cooling, flexible rack connections, general data center cooling
Silicone Can be considered where flexibility is important and temperature performance is demanding
PTFE / PFA More appropriate for applications where chemical resistance, high purity, or specialized coolant compatibility are important
CJAN's portfolio covers multiple hose technologies, while its liquid cooling products specifically include dedicated EPDM‑based data center hoses.

18. CJAN Liquid Cooling Hose Options

CJAN's current website identifies Liquid Cooling Hose / LCH as a dedicated product for liquid cooling systems in data centers.

The current product portfolio also includes:

  • LCH – For general liquid cooling applications
  • LCH‑SD – Fire‑resistant EPDM hose for data center liquid cooling applications
  • LCH‑SDS – Ultra‑flexible fire‑resistant EPDM hose for data center liquid cooling applications
  • CJFLEX HAT – High‑airtightness hose for IDC liquid cooling systems

Product architecture overview:

The final model should still be selected against the customer's actual flow, pressure, temperature, coolant and installation requirements.

19. Questions to Send to a Hose Supplier

When requesting a quotation, engineers should provide more than: “Please quote a 1‑inch liquid cooling hose.”

A better RFQ includes:

Application: AI Data Center / GPU Cooling
Coolant: __________
Operating Temperature: __________
Maximum Temperature: __________
Operating Pressure: __________
Required Flow: __________
Hose ID / Connection: __________
Required Length: __________
Bend Radius: __________
Fitting Type: __________
Quick Disconnect: Yes / No
Fire Resistance: Required / Not Required
Quantity: __________

This information allows the supplier to recommend a realistic configuration instead of simply matching a nominal diameter.


Common Hose Sizing Mistakes

# Mistake Consequence
1 Matching Hose Diameter to Port Size A matching port does not guarantee adequate hydraulic performance.
2 Ignoring Pressure Drop The pump may have sufficient flow capacity but insufficient pressure margin.
3 Ignoring QD Restrictions A restrictive QD can offset the benefit of a larger hose.
4 Making the Hose Too Long Longer routes increase pressure loss and installation complexity.
5 Choosing the Largest Hose Available Oversizing can create unnecessary cost and installation problems.
6 Ignoring Bend Radius Hydraulic performance and mechanical installation must be evaluated together.

Conclusion

Liquid cooling hose sizing should never be reduced to a single question such as:

"What size is the CDU port?"

A reliable selection starts with the cooling requirement and works through the complete hydraulic and mechanical system:

Rack heat load → coolant flow → hose ID → pressure drop → fittings/QD → routing → final assembly

For AI data centers, this approach becomes increasingly important as rack power density increases.

CJAN's current liquid cooling portfolio includes LCH, LCH-SD, LCH-SDS and CJFLEX HAT, allowing different hose constructions to be considered according to the project's requirements.

The key principle is simple:

Don't select the hose by connection size alone. Select the complete cooling hose assembly according to flow, pressure, coolant and installation requirements.

Frequently Asked Questions (FAQ)

Related Articles
back to the top